The link information and communication information of the multiplexed remote sub-master station are not displayed.
No. Item SB/SW Description
1)
Network info.
Network
SB0040
SB0044
SW0046
The network used and the type of the host station are displayed.
NET/10[Loop], Remote I/O master station
NET/10[Bus], Remote I/O master station
When GX Developer is connected to the MELSECNET/H (MELSECNET/10 mode) remote I/O
station, "MELSECNET/H" is displayed.
Type
2) Network No. SW0040 The network number of the host station is displayed.
3) Group No. SW0041 "---" is displayed.
4) Station No. SW0042 The station number of the host station is displayed.
5)
Link
information
Mode SW0043
The operation mode of the host station is displayed.
Online
Offline
Forward loop test
Reverse loop test
Station-to-station test (Station that executes tests)
Station-to-station test (Station to be tested)
6)
F loop status,
Loopback station
SB0091
SB0099
SW0099
The status on the forward loop side is displayed.
F loop status: Normal/Abnormal
Loopback station: Unused/"Station number where loopback is executed"
"---" is displayed for the bus type.
7)
R loop status,
Loopback station
SB0095
SB009A
SW009A
The status on the reverse loop side is displayed.
R loop status: Normal/Abnormal
Loopback station: Unused/"Station number where loopback is executed"
"---" is displayed for the bus type.
8) Link scan time
SW006B
SW006C
SW006D
The maximum/minimum/current values of the link scan time of the host station are displayed. (Unit
[ms])
9)
Communication
information
Communication
status
SB0047
The communication status of the host station is displayed.
Data link being performed (SB0047: Off)
Data link being stopped (SB0047: On)
Constant link
scan
Station type
Remote master station
MELSECNET/H (MELSECNET/10 mode)
remote I/O station
Not set
Actual measurement value (The actual maximum/minimum/current values are
displayed.)
Set
Actual measurement value
(The actual
maximum/minimum/current
values are displayed.)
Constant link scan ±2ms