DISPLAYING DATA 2-13
Historic Data Logging Framework
This portion of the meter’s configuration records ‘standardpower system
parameters such as voltage, current, power, frequency and power factor.
Low, mean and high values are recorded for all parameters. Note that
‘low’ and ‘high’ are different from ‘min’ and ‘max’: low and high are reset
every 15 minutes, whereas min and max are typically long-term
measurements that are only reset by the operator. Similarly, ‘mean’ is
reset every 15 minutes, unlike ‘average’ which is typically an instantaneous
averaging of multiple real-time measurements.
Displayed/Accessible by Default
Description of
Parameter or Function
WinPM MGT
Module
Name
Module
Label
Output
Register Label
Mean L-L Volts, AB
l
SW Demand #5 Vll ab mean Vll ab mean
Mean L-L Volts, BC
l
SW Demand #6 Vll bc mean Vll bc mean
Mean L-L Volts, CA
l
SW Demand #7 Vll ca mean Vll ca mean
Mean L-L Volts, average
l
SW Demand #8 Vll avg mean Vll avg mean
Mean Voltage Unbalance
l
SW Demand #9 V unbal mean V unbal mean
Mean Phase A Current
l
SW Demand #10 I a mean I a mean
Mean Phase B Current
l
SW Demand #11 I b mean I b mean
Mean Phase C Current
l
SW Demand #12 I c mean I c mean
Mean Average Current
l
SW Demand #13 I avg mean I avg mean
Mean Neutral Current
l
SW Demand #14 I4 mean I4 mean
Mean kW total
l
SW Demand #15 kW tot mean kW tot mean
Mean kVAR total
l
SW Demand #16 kVAR tot mean kVAR tot mean
Mean kVA total
l
SW Demand #17 kVA tot mean kVA tot mean
Mean Power Factor lag
l
SW Demand #18 PF lag mean PF lag mean
Mean Power Factor lead
l
SW Demand #19 PF lead mean PF lead mean
Mean Frequency
l
SW Demand #20 Freq mean Freq mean
High L-L Volts, AB
l
Maximum #20 Vll ab high Vll ab high
High L-L Volts, BC
l
Maximum #55 Vll bc high Vll bc high
High L-L Volts, CA
l
Maximum #56 Vll ca high Vll ca high
High L-L Volts, average
l
Maximum #33 Vll avg high Vll avg high
High Voltage Unbalance
l
Maximum #34 V unbal high V unbal high
High Phase A Current
l
Maximum #35 I a high I a high
High Phase B Current
l
Maximum #36 I b high I b high
High Phase C Current
l
Maximum #37 I c high I c high
High Average Current
l
Maximum #38 I avg high I avg high
High Neutral Current
l
Maximum #39 I4 high I4 high